The HIMA F8651X is a high-safety, high-reliability central safety module featuring a powerful processor, rich I/O capabilities, and multiple industrial communication interfaces.
HIMA F8651X is a high-reliability Central Processing Module (Central Module) used in HIMA F8651X safety-related programmable electronic systems (PES). It is designed for safety-critical industrial applications requiring high availability and fault tolerance, supporting applications up to SIL 3 according to IEC 61508.
Product Information
Manufacturer: HIMA
Model: F8651X
Product Type: Safety Central Module / CPU Module
System Compatibility: HIMA H51q-MS, H51q-HS, H51q-HRS systems
Safety Level: SIL 3 (IEC 61508)
Country of Origin: Germany
Technical Specifications
Parameter
Description
Processor
Dual Intel 386EX 32-bit microprocessors
Clock Frequency
25 MHz
Operating System Memory
1 MB Flash-EPROM
User Program Memory
1 MB Flash-EPROM
Data Memory
1 MB SRAM
Communication Interfaces
2 × electrically isolated RS-485 serial interfaces
Power Supply
5 V DC
Current Consumption
Approx. 2 A
Installation Space
8 SU
Diagnostic Display
4-digit matrix display
Watchdog Output
24 V DC safety watchdog output, up to 500 mA
Safety Certification
IEC 61508 SIL 3
Key Features
1. High Safety and Reliability
The F8651X uses a redundant dual-processor architecture with continuous self-monitoring, enabling fail-safe operation in safety-related control applications.
2. Advanced Diagnostics
The module provides:
4-digit diagnostic display
LED status indicators
Fault memory and error identification functions
Reset/acknowledge functions for fault recovery
3. Communication Capability
The F8651X supports serial communication through isolated RS-485 interfaces and can be expanded with communication modules such as the HIMA F8627X for Ethernet-based networking and protocols including SafeEthernet and Modbus TCP.
4. Fail-Safe Operation
Integrated watchdog monitoring and safety-related hardware design provide rapid fault detection and safe shutdown behavior in critical processes.
Application Areas
HIMA F8651X is commonly used in:
Emergency Shutdown Systems (ESD)
Burner Management Systems (BMS)
Process Safety Systems
Chemical and Petrochemical Plants
Oil & Gas Facilities
Power Generation Systems
Railway and Transportation Safety Applications
Industrial Automation Safety Control
Advantages
SIL 3 certified safety performance
High availability and fault tolerance
Long lifecycle support for HIMA H51q systems
Powerful diagnostic capability
Suitable for redundant safety architectures
Designed for continuous industrial operation
Conclusion
The HIMA F8651X Central Module is a robust safety controller component for HIMA F8651X PES platforms. With dual 32-bit processor architecture, integrated diagnostics, redundant safety functions, and SIL 3 compliance, it provides reliable control for demanding safety applications in process industries, energy, and critical infrastructure systems.